• Schneider TMC2TI2 Cartridge M221 - 2 temperature inputs - I/O extension,TMC2TI2

Schneider TMC2TI2 Cartridge M221 - 2 temperature inputs - I/O extension,TMC2TI2, Schneider

 Schneider TMC2TI2 Cartridge M221 - 2 temperature inputs - I/O extension

Main
range of product
Modicon M221
product or component type
Analogue input cartridge
product compatibility
Modicon M221C
analogue input number
2
Complementary
analogue input type
Thermocouple, input range: - 200...1000 °C for thermocouple J
Thermocouple, input range: - 200...1300 °C for thermocouple K
Thermocouple, input range: 0...1760 °C for thermocouple R
Thermocouple, input range: 0...1760 °C for thermocouple S
Thermocouple, input range: 0...1820 °C for thermocouple B
Thermocouple, input range: - 200...400 °C for thermocouple T
Thermocouple, input range: - 200...1300 °C for thermocouple N
Thermocouple, input range: - 200...800 °C for thermocouple E
Thermocouple, input range: 0...2315 °C for thermocouple C
Temperature probe, input range: - 60...180 °C (Ni 100/Ni 1000)
Temperature probe, input range: - 200...850 °C (Pt 100)
Temperature probe, input range: - 200...600 °C (Pt 1000)
analogue input resolution
14 bits
LSB value
0.1 °C
sampling duration
125 ms (thermocouple)
250 ms (temperature probe)
absolute accuracy error
+/- 0.1 % of full scale Pt 100/Pt 1000, Ni 100/ Ni 1000 25 °C
+/- 0.4 % of full scale thermocouple K - 200...0 °C 25 °C
+/- 0.1 % of full scale thermocouple K 0...1300 °C 25 °C
+/- 0.4 % of full scale thermocouple J - 200...0 °C 25 °C
+/- 0.1 % of full scale thermocouple J 0...1000 °C 25 °C
+/- 0.4 % of full scale thermocouple E - 200...0 °C 25 °C
+/- 0.1 % of full scale thermocouple E 0...800 °C 25 °C
+/- 0.4 % of full scale thermocouple T - 200...0 °C 25 °C
+/- 0.1 % of full scale thermocouple T 0...400 °C 25 °C
+/- 0.4 % of full scale thermocouple N - 200...0 °C 25 °C
+/- 0.1 % of full scale thermocouple N 0...1300 °C 25 °C
+/- 6 °C thermocouple R, S 0...200 °C 25 °C
+/- 0.1 % of full scale thermocouple R, S 200...1760 °C 25 °C
+/- 0.1 % of full scale thermocouple C 0...2315 °C 25 °C
temperature drift
+/- 0.02 %FS/°C
repeat accuracy
+/- 0.5 %FS
non-linearity
+/- 0.01 %FS
cross talk
<= 1 LSB
type of cable
Twisted shielded pairs cable
electrical connection
2 screw terminal blocks (pitch 3.81 mm) 1.5 mm² 3 for inputs
cable distance between devices
Twisted shielded pairs cable: 30 m for input
insulation
Non-insulated between analogue input and internal logic
height
41 mm
depth
15 mm
width
35 mm
product weight
0.015 kg
input impedance
>= 1 MOhm
Environment
immunity to microbreaks
10 ms


Write a review

Please login or register to review

Schneider TMC2TI2 Cartridge M221 - 2 temperature inputs - I/O extension,TMC2TI2

  • Brand: Schneider
  • Product Code: TMC2TI2
  • Availability: 1000

Tags: TMC2TI2