Schneider TSXPAY262 Preventa safety module - 24 V DC - standard format - < 5 W,TSXPAY262, Schneider
Schneider TSXPAY262 Preventa safety module - 24 V DC - standard format - < 5 W
range of product |
Modicon Premium Automation platform
|
|
---|---|---|
product or component type |
Preventa safety module
|
[Us] rated supply voltage |
24 V DC
|
|
---|---|---|
supply voltage limits |
19.2...30 V
|
|
activation threshold |
< 20 V
|
|
short-circuit protection |
1 A gG external conforming to IEC 947-5-1 on power supply
4 A gG external conforming to IEC 947-5-1 on safety relay outputs |
|
isolation voltage |
4000 V III 2
|
|
discrete input number |
1 double or single contact selection input conforming to IEC
1131 Type 1
1 feedback loop input conforming to IEC 1131 Type 1 1 reset PB input conforming to IEC 1131 Type 1 1 reset PB monitoring input conforming to IEC 1131 Type 1 12 emergency stop or limit switch discrete inputs conforming to IEC 1131 Type 1 |
|
discrete input logic |
Positive
|
|
inrush current |
<= 0.5 A
|
|
isolation between input and earth |
500 Vrms 50/60 Hz for 60 s
|
|
power dissipation in W |
< 5 W
|
|
safety outputs |
2 NO safety relay AGCDO gold plated volt free output
|
|
[Ue] rated operational voltage |
17...127 V DC relay output
19...250 V AC relay output |
|
rated power in VA |
120 VA 48 V AC-15 inductive
280 VA 110 V AC-15 inductive 550 VA 220 V AC-15 inductive 60 VA 24 V AC-15 inductive |
|
rated power in W |
60 W 24 V DC-13 inductive 100 ms
|
|
[Ithe] conventional enclosed thermal current |
<= 2.5 A
|
|
minimum output current |
>= 30 mA
|
|
response time on output |
< 12 ms
|
|
isolation between output and earth |
300 V conforming to DIN VDE 0110 part 2
1500 Vrms 50/60 Hz for 60 s |
|
safety acquisition |
Monitor external power supply of the module
Read enable inputs Read feedback loop Read the safety outputs control Read status of the 24 inputs |
|
local signalling |
28 LEDs diagnostic of safety system
|
|
electrical connection |
1 connector removable screw terminal block 6 pins for connecting
the safety output
1 connector SUB-D 44 pins for connecting the safety system input |
|
cable cross section |
1.5 mm² with cable end safety output circuit
0.2...2.5 mm² without cable end safety output circuit |
|
current consumption |
< 150 mA 5 V DC
<= 200 mA 24 V DC |
|
module format |
Standard
|
|
product weight |
0.43 kg
|
ambient air temperature for operation |
0...40 °C without fan
0...60 °C with fan module |
|
---|---|---|
ambient air temperature for storage |
-25...70 °C
|
|
IP degree of protection |
IP20 conforming to IEC 60529
|
|
standards |
CSA C22.2 specific requirements (PLC)
EN 954 machine safety parts of control systems EN/IEC 60204-1 machine electrical equipment EN/IEC 61131-2 specific requirements (PLC) EN/ISO 12100 machine electrical equipment ISO 13850 emergency stop equipment UL 508 specific requirements (PLC) ISO 13849-1 category 4 machine safety parts of control systems IEC 61508 SIL 3 machine safety parts of control systems |
|
product certifications |
BG
CSA UL |
Schneider TSXPAY262 Preventa safety module - 24 V DC - standard format - < 5 W,TSXPAY262
- Brand: Schneider
- Product Code: TSXPAY262
- Availability: 1000
Tags: TSXPAY262