• Schneider TM3TM3 Module TM3 - 2 temperature inputs and 1 analog output,TM3TM3

Schneider TM3TM3 Module TM3 - 2 temperature inputs and 1 analog output,TM3TM3, Schneider

Schneider TM3TM3 Module TM3 - 2 temperature inputs and 1 analog output

Main
range of product
Modicon TM3
product or component type
Input/output analog module
range compatibility
Modicon M221
Modicon M251
Modicon M241
analogue input number
2
analogue input type
Current, analogue input range: 4...20 mA
Current, analogue input range: 0...20 mA
Voltage, analogue input range: 0...10 V
Voltage, analogue input range: - 10...10 V
Thermocouple, analogue input range: - 200...1000 °C with thermocouple J
Thermocouple, analogue input range: - 200...1300 °C with thermocouple K
Thermocouple, analogue input range: 0...1760 °C with thermocouple R
Thermocouple, analogue input range: 0...1760 °C with thermocouple S
Thermocouple, analogue input range: 0...1820 °C with thermocouple B
Thermocouple, analogue input range: - 200...400 °C with thermocouple T
Thermocouple, analogue input range: - 200...1300 °C with thermocouple N
Thermocouple, analogue input range: - 200...800 °C with thermocouple E
Thermocouple, analogue input range: 0...2315 °C with thermocouple C
Ni 100/Ni 1000 temperature probe, analogue input range: - 60...180 °C
Pt 100 temperature probe, analogue input range: - 200...850 °C
Pt 1000 temperature probe, analogue input range: - 200...600 °C
analogue output number
1
analogue output type
4...20 mA current
0...20 mA current
0...10 V voltage
- 10...10 V voltage
Complementary
analogue input resolution
15 bits + sign
16 bits
permissible continuous overload
13 V voltage
40 mA current
input impedance
<= 50 Ohm current
>= 1 MOhm temperature probe
>= 1 MOhm thermocouple
>= 1 MOhm voltage
analogue output resolution
12 bits
LSB value
0.15 mV, analogue input: 0...10 V voltage
0.30 mV, analogue input: - 10...10 V voltage
0.30 µA, analogue input: 0...20 mA current
0.244 µA, analogue input: 4...20 mA current
0.1 °C temperature probe
2.44 mV, analogue output: 0...10 V voltage
4.88 mV, analogue output: - 10...10 V voltage
4.88 µA, analogue output: 0...20 mA current
3.91 µA, analogue output: 4...20 mA current
0.1 °C thermocouple
load type
Resistive
load impedance ohmic
1 kOhm voltage
300 Ohm current
stabilisation time
1 ms
conversion time
100 ms + 100 ms per channel + 1 controller cycle time for analogue input thermocouple
100 ms + 100 ms per channel + 1 controller cycle time for analogue input temperature probe
10 ms + 10 ms per channel + 1 controller cycle time for analogue input voltage/current
sampling duration
10 ms for analogue input voltage/current
100 ms for analogue input voltage/current
100 ms for analogue input thermocouple
100 ms for analogue input temperature probe
absolute accuracy error
+/- 0.1 % of full scale at 25 °C for analogue input voltage/current
+/- 0.1 % of full scale at 25 °C for analogue output voltage/current
+/- 0.1 % of full scale at 25 °C for Pt 100/Pt 1000, Ni 100/ Ni 1000 temperature probe
+/- 6 °C at 25 °C for thermocouple R, S 0...200 °C
+/- 0.4 % of full scale at 25 °C for thermocouple K - 200...0 °C
+/- 0.4 % of full scale at 25 °C for thermocouple J - 200...0 °C
+/- 0.4 % of full scale at 25 °C for thermocouple E - 200...0 °C
+/- 0.4 % of full scale at 25 °C for thermocouple T - 200...0 °C
+/- 0.4 % of full scale at 25 °C for thermocouple N - 200...0 °C
+/- 0.1 % of full scale at 25 °C for thermocouple C 0...2315 °C
+/- 0.1 % of full scale at 25 °C for thermocouple R, S 200...1760 °C
+/- 0.1 % of full scale at 25 °C for thermocouple B 300...1820 °C
+/- 0.1 % of full scale at 25 °C for thermocouple K 0...1300 °C
+/- 0.1 % of full scale at 25 °C for thermocouple J 0...1000 °C
+/- 0.1 % of full scale at 25 °C for thermocouple E 0...800 °C
+/- 0.1 % of full scale at 25 °C for thermocouple T 0...400 °C
+/- 0.1 % of full scale at 25 °C for thermocouple N 0...1300 °C
temperature drift
+/- 0.006 %FS/°C
repeat accuracy
+/-0.5 %FS for input
+/- 0.4 %FS for output
non-linearity
+/- 0.01 %FS analog output
+/- 0.1 %FS analog input
output ripple
20 mV
cross talk
<= 1 LSB
[Us] rated supply voltage
24 V DC
supply voltage limits
20.4...28.8 V
type of cable
Twisted shielded pairs cable 30 m for input/output circuit
current consumption
55 mA at 24 V DC (no load) via external supply
55 mA at 5 V DC (no load) via bus connector
60 mA at 5 V DC (full load) via bus connector
80 mA at 24 V DC (full load) via external supply
local signalling
1 LED green for PWR
electrical connection
11 x 2.5 mm² removable screw terminal block with pitch 5.08 mm adjustment for inputs, outputs and supply
insulation
500 V AC between output and internal logic
500 V AC between input and internal logic
1500 V AC between input and supply
1500 V AC between output and supply
marking
CE
surge withstand
1 kV for power supply with common mode protection conforming to EN/IEC 61000-4-5
0.5 kV for power supply with differential mode protection conforming to EN/IEC 61000-4-5
1 kV for I/O with common mode protection conforming to EN/IEC 61000-4-5
0.5 kV for I/O with differential mode protection conforming to EN/IEC 61000-4-5
mounting support
Top hat type TH35-15 rail conforming to IEC 60715
Top hat type TH35-7.5 rail conforming to IEC 60715
Plate or panel with fixing kit
height
90 mm
depth
70 mm
width
23.6 mm
product weight
0.115 kg

Environment
standards
EN/IEC 61010-2-201
EN/IEC 61131-2
resistance to electrostatic discharge
4 kV on contact conforming to EN/IEC 61000-4-2
8 kV in air conforming to EN/IEC 61000-4-2
resistance to electromagnetic fields
10 V/m at 80 MHz...1 GHz conforming to EN/IEC 61000-4-3
3 V/m at 1.4 GHz...2 GHz conforming to EN/IEC 61000-4-3
1 V/m at 2 GHz...3 GHz conforming to EN/IEC 61000-4-3
resistance to magnetic fields
30 A/m conforming to EN/IEC 61000-4-8
resistance to fast transients
1 kV I/O conforming to EN/IEC 61000-4-4
resistance to conducted disturbances
10 V at 0.15...80 MHz conforming to EN/IEC 61000-4-6
3 V at spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to Marine specification (LR, ABS, DNV, GL)
electromagnetic emission
Radiated emissions, test level: 40 dBμV/m QP class A (10 m at 30...230 MHz) conforming to EN/IEC 55011
Radiated emissions, test level: 47 dBμV/m QP class A (10 m at 230...1000 MHz) conforming to EN/IEC 55011
immunity to microbreaks
10 ms
ambient air temperature for operation
-10...55 °C (horizontal installation)
-10...35 °C (vertical installation)
ambient air temperature for storage
-25...70 °C
relative humidity
10...95 % without condensation in operation
10...95 % without condensation in storage
IP degree of protection
IP20
pollution degree
2
operating altitude
0...2000 m
storage altitude
0...3000 m
vibration resistance
3.5 mm at 5...8.4 Hz with DIN rail mounting support
3 gn at 8.4...150 Hz with DIN rail mounting support
shock resistance
15 gn during 11 ms

Write a review

Please login or register to review

Schneider TM3TM3 Module TM3 - 2 temperature inputs and 1 analog output,TM3TM3

  • Brand: Schneider
  • Product Code: TM3TM3
  • Availability: 1000

Tags: TM3TM3